Three Phase High Frequency Online UPS 80-100KVA

3P/3P 400V High Frequency Online UPS 80-100KVA

 

Model Number: CNH330 80 - 100KVA

Nominal Capacity: 80-100KW

Nominal Voltage: 380/400/415VAC

Input Voltage Range: 305 ~ 478VAC; 208 ~ 304VAC(output derated below 70%)

Nominal Frequency: 50/60HZ

  • Numéro d'article :

    CNH330 80 - 100KVA
  • Commande (MOQ) :

    1 pcs
  • Paiement :

    T/T
  • Origine du produit :

    China
  • Couleur :

    Black
  • Port d'expédition :

    Shenzhen
  • Délai de mise en œuvre :

    1 week
  • Lester :

    200 Kg

3P/3P 400V High Frequency Online UPS 80-100KVA

 

Feature:

 DSP technology guarantees high reliability

DSP and MCU dual chips to secure the product reliability.

 

● Output power factor 1

For critical applications,this 3-phase online UPS with output power factor 1.0 ensures higher efficiency and advanced performance.

 

● Adapting the latest Silicon carbide diodes to enhance the system efficiency

Through adapting the latest Silicon carbide diodes,no matter it's in AC mode and battery mode, the efficiency ishigher than 96%.

 

● Dual Inputs

CNH330 series is also available for optional dual inputs to support various in puts to have flexibility for systemconfiguration.

 

● Very powerful charger to shorten the recharge time

Adapting the charger rating equals to 30% of UPS capacity on 10/20Kva.Charger rating is also 20% of UPS capacity for 30Kva and above models.

 

● Adjustable charging current

Users can adjust charging current via LCD setting based on various battery configurations.

 

● Parallel up to 6 units with common battery pack

Supports maximum 6 units in parallel with common battery pack for the parallel system.

 

● 5" color touch type LCD display

Inbuilt 5"color touch type LCD display with 500 event/data logs.

 

● Optional programmable relay dry contact card

Configurable4 dry contact ports definition through software for various applications.

 

● Voice warning / error code notice

Inbuilt the speaker to have human voice for the warning / error codes notice instead oftraditional beeps.

 

● High overload capability

Supporting 110% overload capacity for 60 min and up to 1 min overload condition at 150% load.

 

● Adjustable battery design

The number of connected batteries can be adjusted flexibly based on different power demands.

 

● Dynamic password feature optimizes service performance

This dynamic password is automatically generated from our exclusive utility tool. Each time when it is required to change service-related settings, this utility tool would generate an unique password on time basis. It secures UPS from unexpected operation due to unauthorized settings.

 

● Power walk-in function

 

CNH330 is designed to have flexible power walk-in by way of adjusting the power walk-in time. This setting will optimize generator sizing and reduce the impact to the AC source by having different walk-in time period for different paralleled UPS system when AC grid is recovered.

Technical Parameters:   

Environmental characteristics

Item

Unit

Specifications

Noise within 1 m

dB

Max. 75

Altitude

m

≤1000, derate power by 1% per 100m

Relative humidity

% RH

0 ~ 95, non-condensing

Operating temperature

°C

0 ~ 40°C

Storage and transport temperature for UPS

°C

-15 ~ 60

Mechanical characteristics

Model

 

80K

100K

Rated power (kVA)

Unit

80

100

Dimensions, D x W x H

mm

1000 x 430 x 1200

Weight

kg

200

Color

N/A

Black

Rectifier AC input (mains)

Rated power (kVA)

Unit

80~100

Rated AC input voltage

Vac

380/400/415 (3-phase and sharing neutral with the bypass input)

Input voltage tolerance

Vac

305 ~ 478; 208 ~ 304(output derated below 70%)

Frequency

Hz

50/60 (tolerance: 40Hz ~ 70Hz)

Power factor

kW/kVA

0.99 (0.97) full load(half load)

Harmonic current distortion

THDI%

<4 (full load)

Max. current / phase

A

80kVA/80kW

154

100kVA/100kW

183

Icc

kA

≤ 10kA

Battery 

Intermediate DC circuit

Battery

External battery

Number of lead-acid cells

Nominal

216 (6cells x 36 12V battery block)

Maximum

240 (6cells x 40 12V battery block)

Minimum

192 (6cells x 32 12V battery block)

Float voltage

V/cell

2.28V/cell

Temperature

Compensation

(option)

mV/℃/cl

0~-5

Ripple voltage

% V float

≤1

Ripple current

% C10

≤5

Boost voltage

VRLA

2.35V/cell

EOD voltage

V/cell

1.67-1.83V/cell (adjustable)

Battery charge

V/cell

Constant current and constant voltage charge mode

Battery charging power¹   max current

 A

24A(adjustable) @ 80KVA/100KVA Model

Note:

1. At low input voltage the UPS recharging capability increases and load decreases (up to the maximum capacity indicated).

Inverter output (to critical load)

Rated power (kVA)

Unit

80~100

Rated AC voltage¹

Vac

380/400/415 (three-phase four-wire, with neutral reference to the bypass neutral)

Frequency

Hz

50/60 Auto Selectable

Overload

%

100%~110% for 60min

110%~125% for 10min

126%~150% for 1min

>150% for 200ms

Steady state voltage stability

%

± 1 (balanced load), ± 2 (100% unbalanced load)

Total harmonic voltage

%

<2 (linear load), <4 (non-linear load)

Synchronization window

 

+/- 1Hz, +/- 2Hz, +/- 4Hz (default: 4Hz)

Output rated current

(380/400/415V)

A

80kVA/80kW

121/116/111

100kVA/100kW

152/145/139

Note:

1. Factory setting is 400V. 380 or 415V is selectable by commissioning engineer.

Bypass mains input

Rated power (kVA)

Unit

80~100

Rated AC voltage¹

Vac

380/400/415 (Three-phase four-wire, sharing neutral   with the rectifier input and providing neutral reference to the output)

Overload

%

105%~110% for 60min

110%~125% for 10min

126%~150% for 1min

>150% for 200ms

Upstream protection, bypass line

N/A

Circuit breaker, rated up to 100% of nominal output current.

Frequency

Hz

50/60 Auto Selectable

Transfer time (between bypass 

and inverter)

ms

Synchronous transfer: Line <àBattery 0ms

Inverter <àBypass 0ms

(When phase lock fails, <4ms interruption occurs from inverter to bypass) Inverter <àECO ≤10ms

Bypass voltage tolerance

%Vac

Upper limit: +10, +15 or +20, default: +15

Lower limit: -10, -20, -30 default: -20

Frequency Range

Hz

+/- 1Hz, +/- 2Hz, +/- 4Hz (default: 4Hz)

Note:

1. Factory setting is 400V. 380V or 415V is selectable by commissioning engineer.

 

 

laisser un message
Si vous êtes intéressé par nos produits et souhaitez en savoir plus, veuillez laisser un message ici, nous vous répondrons dès que possible.
soumettre
Produits connexes
Three Phase High Frequency Online UPS 80-100KVA
3P/3P 400V High Frequency Online UPS 80-100KVA   Model Number: CNH330 80 - 100KVA Nominal Capacity: 80-100KW Nominal Voltage: 380/400/415VAC Input Voltage Range: 305 ~ 478VAC; 208 ~ 304VAC(output derated below 70%) Nominal Frequency: 50/60HZ
UPS en ligne haute fréquence triphasé 30-60KVA
UPS en ligne haute fréquence 3P/3P 400V 30-60K   Numéro de modèle : CNH330 30 - 60KVA Capacité nominale : 30-60 KW Tension nominale : 380/400/415VAC Plage de tension d'entrée : 110 – 300 VCA Fréquence nominale : 50/60 HZ
UPS en ligne haute fréquence triphasé 10-20KVA
UPS en ligne haute fréquence 3P/3P 400V 10-20K   Numéro de modèle : CNH330 10 - 20 KVA Capacité nominale : 10 à 20 KW Tension nominale : 380/400/415VAC Plage de tension d'entrée : 110 – 300 VCA Fréquence nominale : 50/60 HZ

Besoin d'aide? Discute avec nous

laisser un message
Si vous êtes intéressé par nos produits et souhaitez en savoir plus, veuillez laisser un message ici, nous vous répondrons dès que possible.
soumettre
CONTACTEZ-NOUS #
0086 13501592453

Nos horaires

Lun 21/11 - Mer 23/11 : 9h00 - 20h00
Jeu 24/11 : fermé - Joyeux Thanksgiving !
Ven 25/11 : 8h00 - 22h00
Sam 26/11 - Dim 27/11 : 10h - 21h
(toutes les heures sont en heure de l'Est)

Maison

Des produits

whatsApp

contact